Greenheck Fan CSP Ventilation Hood User Manual


 
DELUXE CEILING FAN
B
SP
STANDARD CEILING FAN
C
SP
17
HVI CFM/Static Pressure in inches of WG
Model RPM AMPS Watts
Sones 0.000 0.100 0.125 0.250 0.375 0.500 0.625 0.750 1.000
CFM 67 53 51 40 29
SP-B50 625 0.50 38 1.4
Sones 1.7 1.9 1.9 2.6 3.5
CFM 77 70 68 57 49 39
SP-B70 675 0.53 45 1.4
Sones 1.7 1.9 1.9 2.4 3.1 3.6
CFM 87 80 78 68 61 54 44 30
SP-B80 900 0.60 54 2.5
Sones 2.9 2.9 3.0 3.2 3.6 4.3 5.5 5.6
CFM 102 92 88 75 59 45 30
SP-B90 700 0.65 50 2.0
Sones 1.9 2.6 2.7 3.0 3.6 4.1 4.9
CFM 133 114 110 97 95 94 91 85 50
SP-B110 950 1.14 80 1.5
Sones 2.0 2.1 2.2 2.4 2.7 2.8 3.6 4.4 5.4
CFM 160 156 155 154 152 149 147 138 92
SP-B150 1050 1.70 129 2.5
Sones 3.0 3.3 3.3 3.7 4.3 4.5 5.0 5.3 5.8
CFM 197 195 194 191 187 184 181 166 128
SP-B200 1100 2.20 173 4.0
Sones 4.4 4.6 4.7 5.1 5.6 5.8 6.0 6.3 6.6
Performance Data
Dimensional Data
*Add 1½ inches to C dimension for incandescent light.
Mounting bracket width is 1½ inch
For complete dimensional information, see CAPS submittal drawings.
All dimensions are in inches.
Model
A B C
D E F Grille Wt.
50 7
1
/2 7
1
/2 3
5
/8 3 1
5
/8
1
/2 9
1
/4 x 9 5
Performance certified is for Model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed
(RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated
per AMCA Standard 301. Values are for installation type B: free inlet fan sone levels.
Performance Data
CFM/Static Pressure in inches of WG
Model RPM AMPS Watts
0.00 0.100 0.125 0.250 0.375 0.500 0.625
CFM 52 49 48 46 43 37 29
SP-C50 1680 0.80 46
Sones 2.9 3.6 3.6 3.9 4.2 4.8 6.3
Dimensional Data
For complete dimensional information, see CAPS submittal drawings.
All dimensions are in inches.
Performance certified is for Model SP exhaust for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed
(RPM) shown is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated
per AMCA Standard 301. Values are for installation type B: free inlet fan sone levels.
5 UL Listed for use above tubs.
6 Available with 277 volt motor.
1 HVI sones at 0.1 wg
2 Available with light
3 Available with CRD - Ceiling Radiation Damper
4 Available with 50 Hz motors (See CAPS for performance)
Designer Decorative Unit
Model A B *C D E
Grille Grille Wt.
50, 70, & 80 13
7
/8 11
1
/2 6
15
/16 4
3
/4 14
7
/8 x 13
1
/4 15
1
/4 sq. 9
90, 110, 150, 200 13
7
/8 11
1
/2 7
15
/16 6 1
1
/4 14
7
/8 x 13
1
/4 15
1
/4 sq. 10
1
2,3,5
2,3,5
2,3,4,5,6
3,4,5,6
2,3,4,5,6
2,3,4,5
2,3,5
A
B
C
D
E
A
B
C
D
E
F
®
®