TrueFRESH™ ERV/HRV Ventilation Systems 69-2480EF—05
16
Installation Steps (continued)
5
Installing the condensation drain line
Insertthethreadeddrainadapterthroughthebottomof
the unit and hand tighten the plastic nut supplied with
the drain kit.
Use a wrench to tighten the nut another half turn to
ensure a complete seal.
Installthecondensatetubingbypushingtheclear
plastictubingoverthedrainadapter.
Makeacondensatetrapbyloopingtheclearplastic
tubing.Thisloopwillpreventfoulodorsfromentering
the unit.
Use a condensate pump if you don’t have access to
the floor drain.
Drainless Application
NOTE: If installing an ERV unit (VNT5150E1000 or VNT5200E1000) in a region where the outdoor
temperaturedoesnotdropbelowfreezing,thecondensatedrainlinedoesnotneedtobe
installedandtheunitmaybeinstalledasadrainlessapplication.
1. Insertthethreadeddrainadapterthroughthebottom
of the ERV with the drain connection inside of the unit
asshowninthegure.
2. Fittherubberwasheroverthedrainadapterandthen
attach the plastic nut.
3. Hand tighten the plastic nut supplied with the drain kit.
4. Use a wrench to tighten the nut another half turn to
ensure a complete seal.
5. Attach the drain cap to the drain adapter inside the
unit.