Honeywell 69-2480EF05 Ventilation Hood User Manual


 
Specications
Dimensions in inches (mm):
InstalltheERV/HRVVentilationSystemaccordingtonationalandlocalregulations,building,andsafety
codes.
StandardsandCertications:
Model Product Weight Shipping Weight Heat/Energy Core
Dimensions
Filter Dimensions
VNT5150H1000
VNT5150E1000
42lbs.(19kg) 47.5lbs.(21.55kg)
H = 12 in. (305 mm)
W = 10 in. (254 mm)
L = 12 in. (305 mm)
H = 12 in. (305 mm)
W = 10 in. (254 mm)
VNT5200H1000
VNT5200E1000
50lbs.(22.68kg) 57.5lbs.(26.08kg)
H = 12 in. (305 mm)
W = 15 in. (381 mm)
L = 12 in. (305 mm)
H = 12 in. (305 mm)
W = 15 in. (381 mm)
PhysicalSpecications:
VNT5150H1000 or VNT5150E1000: H = 22 1/2 in. (572 mm), W = 11 1/2 in. (295 mm), L = 29 1/2 in. (749 mm)
VNT5200H1000 or VNT5200E1000: H = 22 1/2 in. (572 mm), W = 16 1/2 in. (422 mm), L = 29 1/2 in. (749 mm)
FRONT CLEARANCE OF 25 INCHES
(635 MM) IS REQUIRED FOR
SERVICING UNIT.
ALL DUCT CONNECTIONS ARE
6 IN. (150 MM).
2
1
H
W
L
1
2
M28919
TrueFRESH™ ERV/HRV Ventilation Systems 69-2480EF—05
4
• Drain tubing diameter: 1/2 in. (12.7 mm)
• Flexible Duct (2):6in.roundforinletandoutlet.Flexiblevinyl,compatibleforconnectiontorigidor
flexibleductingwithsheetmetalscrewsand/ortape.
• Cabinet:20gaugegalvanizedsteel
Operating Ranges:
AmbientTemperature:34to135ºF(1to57ºC)
Humidity: 0-99% RH
Electrical Ratings:
InputVoltage:120VAC,60Hz
Input Current: 1.5 A
Output Power to Terminals: 5 VDC, 1.0 A
maximum