MAINTENANCE
CAUTION: Disconnect electrical power before performing any of the following maintenance
procedures.
The Chiller will require very little normal maintenance.
1. On AIR-COOLED Chillers, the condenser fins should be cleaned by blowing compressed air through the
condenser from the fan side as required to eliminate any dirt or debris that may accumulate over time. This
can severely reduce the performance of the Chiller. Cleanable air filters are available as an option. Contact
the factory for information.
2. On AIR-COOLED Chillers the condenser fan motor should be lubricated every 6–months with a few drop
of SAE10 oil.
3. The pump motor should be lubricated with thirty drops of SAE20 oil once a year.
4. The circulation system should be drained and flushed periodically to avoid build-up and possible restric-
tion of flow by contaminates.
5. The strainer at the Chiller inlet should be removed and cleaned monthly.