Liebert iCOM Control—Firmware Version XP1.00.010.STD
36
Figure 33 Sensor Data screen, page 1 of 2
Sensor A Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor A.
Sensor A Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor A Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor B Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor B.
Sensor B Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor B.
Sensor B Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor B.
Supply Refrigerant Temperature—Displays the actual supply refrigerant temperature from the
Liebert XDP to the modules.
Supply Chilled Water Temperature—Displays the actual the Supply Chilled Water temperature
to the Liebert XDP.
SENSOR DATA (page 1 of 2) UNIT 01
U301
U302
U303
U304
U305
U306
U307
U308
U309
U310
U311
U312
This window is READ ONLY
Sensor A Temperature 62.8°F
Sensor A Humidity 42.20%
Sensor A Dew Point 39.4°F
Sensor B Temperature 71.2°F
Sensor B Humidity 29.60°%
Sensor B Dew Point 37.8°F
Supply Refrigerant Temperature 55.0°F
Supply Chilled Water Temperature 55.0°F