Mitsubishi Electronics LGH-F-RX3-E Ventilation Hood User Manual


 
LGH-F-RX3-E (Feb. 2009)
LGH-F-RX3-E
Performance Certied
to ARI 1060 Standard
ERV-24
Use Lossnay
®
M-NET remote controllerPZ-52SF-E.
(Do not use PZ-41SLB-E).
Lossnay
®
transmission connection terminal
Two remote controller system with multiple Lossnay units
It is also possible to operate two remote controller units when using
multiple Lossnay
®
units.
Power supply
Power supply
Remote controller
PZ-41SLB-E
Interlocking multiple units
When the operation signal is an uncharged a-contact signal
Interlocking/individual joint systems
By making the group setting, interlock settings have become possible.
(Joint use of the CITY MULTI
®
remote controller and Lossnay remote
controller is possible.)
Interlocking is possible from multiple air conditioning units, etc.
(excluding pulse input)
(Separately sold parts are necessary depending on the operation signal).
Applicable indoor units use MA remote contoller models.
Do not set the air conditioning unit and Lossnay
®
unit to be
part of the same group.
When the address number has been changed, the data in the memory
is automatically reset.
Power supplyPower supply Power supply Power supply
Lossnay
®
A/CA/C A/C
Remote
controller
PZ-41SLB-E
Air conditioning
unit side remote
controller
Air conditioning
unit side remote
controller
Air conditioning
unit side remote
controller
Indoor unit
(01)
Centralized
controller
AG-150A
(201)
Outdoor
unit (51)
Operation settings
MA remote
controller
Lossnay (02)
Lossnay M-NET
remote controller
(PZ-52SF-E)(102)
Group 1Group 2
Use Lossnay
®
remote controller PZ-41SLB-E
(Do not use PZ-52SF-E).
Lossnay
®
transmission connection terminal
ABS65654321
ABS A65BS
0
1
SA1 SA2
0
2
0
1
SA1 SA2SA1 SA2
Transmission cable
Transmission
cable
Round terminal
M-NET transmission cable
input terminal block
Shielded wire
M-NET
transmission cable
Remote controller input terminal
Main/Sub selection switch
(SW1)
Main Sub
(Set to Main when
shipped from the factory)
( ) address
LGH-F300, F470
andF600RX types
LGH-F1200RX type
LGH-F300, F470
and F600RX types
TB5
LGH-F1200RX type
TB5
Setting
Setting
LGH-F300, F470 and F600RX types LGH-F1200RX type
Upper
circuit
board
[Sub]
ex. SA1 = 0,
SA2 = 2
Lower
circuit
board
[Main]
ex. SA1 = 0,
SA2 = 1
Operating with external device
The operation of the Lossnay
®
will be connected with the operation or
stopping of the external device.
Input of level signal or pulse signal (12V DC, 24V DC, uncharged a-
contact) is possible.
One Lossnay
®
with one remote controller
One Lossnay
®
unit is operated independently with
one remote controller.
Multiple Lossnay
®
units with one remote controller
Up to 15 Lossnay
®
units can be controlled at
one time with one remote controller.
Two remote controller system with one Lossnay
®
The Lossnay
®
can be controlled from two remote
locations.
The remote controller gives priority to the last
touch.
Operating with Mr. Slim
®
(A-control) - Interlocked
The Remote controller (A-control) controls the air conditioning device and
the Lossnay
®
.
It is possible to operate or switch fan speed for the
Lossnay
®
individually.
Lossnay
Non-polar
2 wires
Remote controller
PZ-41SLB-E
Power supply
Lossnay
Non-polar
2 wires
Power supply
Remote
controller
PZ-41SLB-E
(Sub)
(Main)
Lossnay
Power supply
Lossnay
Non-polar
2 wires
Remote controller
PZ-41SLB-E
Power supply
Air conditioning device
and system control
It is possible to operate
16 indoor units per 1 Lossnay
®
Indoor
unit
MA remote controller
Outdoor unit
Indoor
unit
MA remote controller
Lossnay
®
Indoor
unit
MA remote controller
Lossnay
®
Indoor
unit
Indoor
unit
MA remote controller
Indoor
unit
MA remote controller
Lossnay
®
Indoor
unit
MA remote controller
Indoor
unit
MA remote controller
Lossnay
®
Indoor unitIndoor unit
Group 1 Group 5Group 3 Group 4Group 2
Outdoor unit Outdoor unit
Indoor
unit
MA remote controller
Lossnay
®
Lossnay
®
Group 1
Lossnay
®
3 puorG2 puorG
Control of start/stop, fan speed and ventiliation mode is possible from the Lossnay
®
M-NET remote controller PZ-52SF- E
Control of start/stop, fan speed and ventiliation mode is possible from the centralized controller.
It is possible to set a maximum of 16 units for 1 group.
Lossnay
®
M-NET
remote controller
PZ-52SF-E
Lossnay
®
Lossnay
®
Group 1
Lossnay
®
M-NET
remote controller
PZ-52SF-E
Lossnay
®
Lossnay
®
Lossnay
®
Lossnay
®
Group 3
Lossnay
®
M-NET
remote controller
PZ-52SF-E
Lossnay
®
Group 4Group 2
Power
supply
unit
Lossnay
®
M-NET
remote controller
PZ-52SF-E
Lossnay
®
Group 5
Lossnay
Power supply
Power supply
Remote
controller
Mr. Slim
(indoor unit)
Lossnay
®
Power supply
Power supply
Remote controller
Indoor unit
Remote controller
PZ-41SLB-E
Non-polar
two wires
Note: In the LGH-F1200RX type, there are two circuit boards installed in each unit,
so count each unit as two Lossnay
®
units.
Selection of inter-
locked operation
mode is possible.
Delayed start inter-
locked operation is
possible.
Centralized controller AG-150A
PAR-21MAA
CENTRALIZED CONTROLLER AG-150A
CENTRALIZED CONTROLLER AG-150A
9. SYSTEM CONTROL EXAMPLES
Basic System – Stand-alone Lossnay
®
ERV with PZ-41SLB-E Remote Controller
Operation with Mr. Slim
®
CITY MULTI
®
and Lossnay
®
Interlocked
M-NET SYSTEM
Centralized Management System