Monessen Hearth VFCS30DNV Oven User Manual


 
16 58D6002
Label all wires prior to
disconnection when
servicing controls.
Wiring errors can cause
improper and dangerous
operation. Verify proper
operation after servicing.
ELECTRICAL WIRING (MILLI-VOLT)
Themilli-voltvalveisaself-poweredcombinationgascontrolTHAT DOES NOT REQUIRE 110 VAC TO OPERATE.
On/Off
Switch
On/Off
Switch
ODS
Pilot
Wall
Switch
Optional Wall
Switch or
Remote
ODS Pilot
Millivolt
Valve
Spade Terminal
3
1
2
CONNECTION
1 = TP
2 = TP, TH
3 = TH
Figure 13 - Wiring Diagram
CONNECTING OPTIONAL WALL SWITCH
1. Use18awg,two-wirecable,15feetmaximumlength.
2. Atoneendofthecable,connectbothwirestothewallswitch.Attheotherend,connectonewiretoTP/THandone
wiretoTH,orconnectthewallswitchtothetwomale(0.25")terminalsontheleftsideoftheunit.Thecolorofthe
wires does not matter.
A. COMPLETE MILLIVOLT SYSTEM CHECK
("A" Reading - On/Off switch contacts CLOSED - Control Knob “ON” - Main Burners should turn ON)
a. Ifthereadingismorethan175millivoltsandtheautomaticvalvestilldoesnotcomeon-replacethevalve.
b. Iftheclosedcircuitreading("A"reading)islessthan175millivolts,determinecauseforlowreading-proceedas
follows:
B. THERMOPILE OUTPUT READING CHECK
(“B” Reading - On/Off switch contacts OPEN - Main burner OFF)
Checkgaspressuretotheunit.Ifgaspressureiswithinminimumandmaximumondataplate,thenreplacepilot.Ifthe
minimummillivoltreadingisnotobtainable,replacepilot.
CHECKING SYSTEM OPERATION
The millivolt system and individual compo-
nentsmaybecheckedwithamillivoltmeter
having a 0-1000mv range. Conduct each
checkshowninchartbyconnectingmeter
test leads to terminals as indicated.
Switch
CHECK
TEST
TO TEST CONNECT METER
LEADS TO TERMINALS
METER READING
SHOULD BE
A COMPLETE 2 & 3 SYSTEM MINIMUM 175mv
B THERMOPILE
OUTPUT
1 & 2 SYSTEM 500mv OR MORE