Commissioning
When the hob has been fully installed it will be necessary
to check the minimum flame setting. To do this, follow
the procedure below.
- Turn the gas tap to the MAX position and ignite.
- Set the gas tap to the MIN flame position then turn
the control knob from MIN to MAX several times. If
the flame is unstable or is extinguished follow the
procedure below.
Procedure:
Re-ignite the burner and set to MIN.
Remove the control knob.
The adjustment screw is located down the centre
of the gas tap control shaft or on the lower right
hand side of the shaft (see diagram).
To adjust, use a thin bladed screwdriver and turn
the adjustment screw until the flame is steady
and does not extinguish, when the knob is turned
from MIN to MAX. Repeat this procedure for all
burners.
Pressure Testing
Remove left hand pan support and front left burner
cap and crown.
Fit manometer tube over the injector.
Turn on the burner gas supply and ignite another
burner supply.
The pressure reading should be nominally 20mbar
and must be between 17 mbar and 25mbar.
Turn off the burner supplies.
a) Minimum adjustment screw
b) Tap
FO 1032