Vent Congurations
Toreduceprobabilityofreversedraftingduringshut-down
conditionsHearth&HomeTechnologiesstronglyrecom-
mends:
• Installingthepelletventwithaminimumverticalrun
of1.52m.Preferablyterminatingabovetheroofline.
• Installingtheoutsideairkitatleast1.22mbelowthe
venttermination.
Topreventsootdamagetoexteriorwallsofthehouseand
topreventre-entryofsootorashintothehouse:
• Maintainspeciedclearancestowindows,doorsand
airinlets,includingairconditioners.
• Ventsshouldnotbeplacedbelowventilatedsofts.
Runtheventabovetheroof.
• Avoidventingintoalcovelocations.
• Ventsshouldnotterminateunderoverhangs,decks
orontocoveredporches.
• Maintainminimumclearanceof152mmfromthevent
terminationtotheexteriorwall.Ifyouseedeposits
developingonthewall,youmayneedtoextendthis
distancetoaccommodateyourinstallationconditions.
Negativepressureresultsfromtheimbalanceofairavail-
ablefortheappliancetooperateproperly.Itcanbestron-
gestinlowerlevelsofthehouse.
Causesinclude:
• Exhaustfans(kitchen,bath,etc.)
• Rangehoods
• Combustionairrequirementsforfurnaces,waterheaters
andothercombustionappliances
• Clothesdryers
• Locationofreturn-airventstofurnaceorairconditioning
• Imbalancesoftheheating/coolingairhandlingsystem
• Upperlevelairleakssuchas:
- Recessedlighting
- Attichatch
- Ductleaks
WARNING! Risk of Asphyxiation! Negativepressurecan
causespillageofcombustionfumesandsoot.
C. Negative Pressure
NOTICE: Hearth&HomeTechnologiesassumesno
responsibilityfortheimproperperformanceofthechimney
systemcausedby:
• Inadequatedraftduetoenvironmentalconditions
• Downdrafts
• Tightsealingconstructionofthestructure
• Mechanicalexhaustingdevices
D. Draft
Tominimizetheeffectsofnegativeairpressure:
• Installtheoutsideairkitwiththeintakefacingprevailing
windsduringtheheatingseason
• Ensureadequateoutdoorairforallcombustionappliances
andexhaustequipment
• Ensurefurnaceandairconditioningreturnventsarenot
locatedintheimmediatevicinityoftheappliance
• Avoidinstallingtheapplianceneardoors,walkwaysor
smallisolatedspaces
• Recessedlightingshouldbea“sealedcan”design
• Attichatchesweatherstrippedorsealed
• Atticmountedductworkandairhandlerjointsandseams
tapedorsealed
Onnominalheatoutputthecombustionbloweroperatesat
2053rpmdeveloping0.33m^3/s.Thisistheminimumrequire-
mentforthesupplyofcombustionair.
Draftisthepressuredifferenceneededtoventappliances
successfully.Whenanapplianceisdraftingsuccessfully,all
combustion byproducts are exiting the home through the
chimney.
Installthroughthewarmairspaceenclosedbythebuilding
envelope.Thishelpstoproducemoredraft,especiallydur-
inglightinganddie-downofthere.
Considerationsforsuccessfuldraftinclude:
• Preventingnegativepressure
• Locationofapplianceandchimney
Tomeasurethedraftornegativepressureonyourappliance
useamagnahelicor adigitalpressuregauge capableof
reading0-.13mmofwatercolumn(W.C.).
Theapplianceshouldberunning onhighforatleast15
minutesforthetest.
Withthestoverunningonhighyoushouldhaveanegative
pressureequaltoorgreaterthanthenumbergiveninthe
chartbelow.Ifyouhavealowerreadingthanyoundonthe
chart,yourappliancedoesnothaveadequatedrafttoburn
thefuelproperly.
Minimum Vacuum Requirements: .095