Smeg SA9065LPG Cooktop User Manual


 
Instructions for the installer
7
3. GAS CONNECTION
This appliance is suitable for installation with
Natural Gas or ULPG (propane). Refer to page 12
for the relevant burner pressure and appropriate
injector sizes. When the appliance is to be
connected to Natural Gas then the pressure
regulator supplied must be fitted to the gas inlet. A
test point (for checking the gas pressure) is
supplied either with the regulator or as a separate
fitting in the case of ULPG (propane) appliances.
Connection of the appliance to the gas supply must
be in accordance with the requirements of AS5601.
A ½” BSP connector at the inlet is recommended
and the gas supply line to the appliance must be of
adequate length to allow sufficient withdrawal of
appliance for service or disconnection and be:
1. annealed copper pipe or;
2. flexible hose according to AS/NZ1869 & be at
least Class “B”, 10 mm diameter.
The appliance must be installed with provision to allow the gas to be
turned off and disconnected for servicing and removal of the appliance
as required from the gas supply.
Before the appliance is operated make certain all relevant parts are
placed in the correct position.
When the installation is completed the installation connections of
appliance will require to be leak tested, the burner operating pressure
and flame checked and adjusted.
Warranty service calls do not cover these adjustments!
To check the operating pressure of the appliance it is recommended at
least 2 large size burners are used. Ensure appliance is secured to wall
when installation is completed.
N.G. The regulator supplied must be fitted to the ½ BSP thread at the
rear of the appliance. An approved manual shut-off valve must be
installed. The N.G. regulator must be checked and adjusted to 1.0kPa
after installation.
ULPG: Can be connected to the inlet fitting
directly. The pressure must be checked to
ensure it is operating at 2.75kPa. A separate
test point fitting must be installed between the
piping & the appliance for the pressure to be
checked to ensure it is operating at 2.75kPa.