Wolf Customer Care 800.222.7820
Planning Information
Refer to the illustrations on the following pages for instal-
lation of integrated modules. For induction and electric
modules, refer to the previous cooktop sections.
ELECTRICAL
When multiple cooktops or modules are installed side by
side, each must have its own separate electrical supply.
ELECTRICAL REQUIREMENTS
ELECTRIC MODULES
Electrical Supply grounded 3-wire, 240/208 VAC, 60 Hz
Steamer, Fryer 15 amp dedicated circuit
Induction, Electric, Grill 20 amp dedicated circuit
Conduit exible 4'
(1.2 m)
GAS MODULES
Electrical Supply grounded, 120 VAC, 60 Hz
Service 15 amp dedicated circuit
Receptacle 3-prong grounding-type
Power Cord 6'
(1.8 m)
RANGES / RANGETOPSVENTILATION COOKTOPS OVENS / WARMING DRAWERSOUTDOOR GRILLS
WOLF INTEGRATED MODULES
DRAIN OUTLET
Steamer and fryer modules require a method for draining
hot water and oil. For the steamer module, options include
connecting a drain hose from the
5
/8" (16) outlet tied into
an existing drain, a separate drain with freefall or placing a
heat-resistant receptacle under the drain outlet. For the fryer
module, the drain outlet must be accessible to drain oil into
heat-resistant receptacle.