Toshiba AD268 Coffeemaker User Manual


 
72
Analog I/O Modules (AD268 / DA264 / TC218)
5. I/O Allocation and Programming
PART 3 TC218
Thermocouple (type J) input:
A/D conversion data
Input
temperature
Hexadecimal Integer
Resolution
Burnout detection - H7FFF 32767
Upper limit
+1200 °C
H5DC0 24000
:: :
Full scale (positive)
+800 °C
H3E80 16000
:: :
+0.05 °C
H0001 1
0 0 V H0000 0
-0.05 °C
HFFFF -1
:: :
Full scale (negative)
-200 °C
HF060 -4000
:: :
Lower limit
-210 °C
HEF98 -4200
0.05 °C / bit
D = 20 × A
D: Digital data
A: Temperature (°C)
0
Temperature
HF060
-4000
Digital vale
-200°C
Upper limit
+800°C
H3E80
16000
Lower limit
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net