User’s Manual
75
PART 3 TC218
6. Parameters
6. Parameters
The TC218 has the memory that stores the control parameters, input type designation, module
status information, etc. This memory is called the buffer memory. To access (read/write) this
memory from the T2 program, READ and WRITE instructions are used.
6.1 Memory map
The contents of the TC218's buffer memory are as follows.
Address Contents
F0
H8000 Gain calibration value for channel 1
H8001 Gain calibration value for channel 2
H8002 Gain calibration value for channel 3
H8003 Gain calibration value for channel 4
H8004 Gain calibration value for channel 5
H8005 Gain calibration value for channel 6
H8006 Gain calibration value for channel 7
H8007 Gain calibration value for channel 8
H8008 Offset calibration value for channel 1
H8009 Offset calibration value for channel 2
H800A Offset calibration value for channel 3
H800B Offset calibration value for channel 4
H800C Offset calibration value for channel 5
H800D Offset calibration value for channel 6
H800E Offset calibration value for channel 7
H800F Offset calibration value for channel 8
H8010 Averaging times for channel 1
H8011 Averaging times for channel 2
H8012 Averaging times for channel 3
H8013 Averaging times for channel 4
H8014 Averaging times for channel 5
H8015 Averaging times for channel 6
H8016 Averaging times for channel 7
H8017 Averaging times for channel 8
H8018 Input type setting for channel 1
H8019 Input type setting for channel 2
H801A Input type setting for channel 3
H801B Input type setting for channel 4
H801C Input type setting for channel 5
H801D Input type setting for channel 6
H801E Input type setting for channel 7
H801F Input type setting for channel 8
H8020 Command register
H8021 Response register
H8022
:
H8027
No use
Use WRITE instruction to write
data into these addresses.
Use READ instruction to read
data from this address.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net