![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/1/09/1099e681-efd7-41c9-a090-4ab454e9c0df/1099e681-efd7-41c9-a090-4ab454e9c0df-bga.png)
3200 Series
10 ACS 3216 Operators Manual
6.1.4 To Select Access Level 3 or Configuration Level
Do This The Display You Should See Additional Notes
1. From any display press and hold
for more than 5 seconds
To Select Level 3
Lev 3
goto
0
COD E
The display will pass from the current operating level, for
example, Lev 1 to Lev 3 as the button is held down.
(If no button is then pressed for about 50 seconds the display
returns to the HOME display)
2. Press
or
to enter
the passcode for Level 3
11
CODE
The Level 3 code is 11:
If an incorrect code is entered the display reverts to ‘got o ’.
The controller is now in the level 3 will then revert to the HOME
display
3. When the LEV3 GOTO view is
shown, as in paragraph 1 above, press
to select ‘Conf’
To Select Configuration level
Conf
goto
0
COD E
Note:
must be pressed quickly (within 2 seconds) before
the controller requests the code for level 3
(If no button is then pressed for about 50 seconds the display
returns to the HOME display)
4. Press
or
to enter the
passcode for Configuration level
111
code
Conf
The configuration code is 111:
If an incorrect code is entered the display reverts to ‘goto’.
The controller is now in Configuration level will now show
Conf
5. Press and hold
for more than 3
seconds
6. Press
to select the required level
eg LEV 1
To Return to a Lower Level
Conf
goto
Lev1
goto
The choices are:
LEV 1 Level 1
LEV 2 Level 2
LEV 3 Level 3
ConF Configuration
It is not necessary to enter a code when going from a higher level
to a lower level.
Alternatively, press
and scroll to the Acces list header,
then press
to select the required level.
The display will then flash ‘ConF’ for a few seconds and the
controller will then go through its start up sequence, starting in
the level selected.
Do not power down while Conf is flashing. If a power down
does occur an error message will appear.
☺
A special case exists if a security code has been
configured as ‘0’ If this has been done it is not necessary to
enter a code and the controller will enter the chosen level
immediately.
☺ When the controller is in configuration level the
ACCESS list header can be selected from any view by
holding down the
button for more than 3 seconds.
Then press
again to select ‘ACCES’