Alto-Shaam Gas Fryer Fryer User Manual


 
MN-35207 • Gas Fryer Operation & Care Manual • 6
INSTALLATIONINSTALLATION
VENTILATION
1. A single ASF-60G auto-lift gas fryer requires a
minimum of 120 CFM make-up air for natural gas and
48CFMforpropanegas.Kitchenventilationmustbe
of sufficient capacity to prevent a negative-pressure
condition. DO NOT obstruct or restrict ventilation nor
the air flow required to support combustion.
2. DO NOTobstructtheflowoftheexhaustflueatthe
top rear of the fryer. It is especially critical that gas
supply piping and electrical support cord and/or
receptacle be routed away from the path of the hot
combustion fumes.
3. This fryer cannot be direct vented.
4. Install the fryer under a ventilation hood meeting all
applicable code requirements. Combustion fumes
must be vented in accordance with local, state, or
national codes.
An adequate ventilation system is required for commercial cooking equipment. Information may be obtained by writing
totheNationalFireProtectionAssociation,BatterymarchPark,Quincy,MA02269.WhenwritingrefertoNFPANo.96.
DANGER
Installation, air adjustment and/or
service work must be in accordance
with all local codes and must be
performed by a certifi ed service
technician qualifi ed to work on
gas appliances.
CAUTION
To prevent malfunction or cause
negative back draft, DO NOT obstruct
exhaust fl ues or attach any fl ue
extension that will impede proper
burner operation.
DANGER
FAILURE TO VENT THIS FRYER PROPERLY
MAY BE HAZARDOUS TO THE
HEALTH OF THE OPERATOR.
Equipment damage and operational problems
may also be the consequence of improper venting.
Any damages sustained by a failure to properly vent
this fryer are not covered under warranty.
Ventilatinghoodsandexhaustsystemsshallbepermittedtobe
used to vent appliances installed in commercial applications.
Whereautomaticallyoperatedappliancesareventedthrougha
ventilatinghoodorexhaustsystemequippedwithadamperor
withapowermeansofexhaust,provisionsshallbemadetoallow
theowofgastothemainburnersonlywhenthedamperisopen
to a position to properly vent the appliance and when the power
meansofexhaustisinoperation.
in accordance With nfpa 54
coMMonWealth of Massachusetts only.