InRow RP Technical Data Manual6
Optional Features
Cable Water Detector
A leak detection cable is placed on
the floor or subfloor around all
possible leak sources. If water or
other conductive liquids contact the
cable anywhere along its length, the
microprocessor controller announces
the leak visually, audibly, and across
the network. The 6.1 m (20 ft) cable
may be cascaded to make custom
lengths up to 24.4 m (80 ft).
Network Cable
Various lengths of network cable are
available to ship with your cooling
system. The network cable is used to
interconnect multiple cooling units in
a redundant group, as well as to
connect the network management
card to your LAN.
85% ASHRAE 52.1 Filter
Electrical equipment requires clean,
particle free air, thus making the
filtration of the air extremely
important. Optionally, the system
uses a 85% efficient, 100 mm (4 in),
deep loading, pleated filter. Deeper
filters produce a lower pressure drop,
requiring less energy during normal
operation. The 100% synthetic media
will not absorb moisture and is
resistant to most common chemicals.
The filter is moisture resistant up to a
100% relative humidity. Filters are
easily replaceable from the rear of
the unit. (MERV 13 per ASHRAE
52.2, EN779 F7)
Power Trough
Overhead power distribution between
adjacent NetShelter racks allows for
removal of the InRow RP without
disrupting overhead power cabling.
Data Partition
Overhead cable distribution between
adjacent NetShelter racks allows for
removal of the InRow RP without
disrupting overhead cabling.
Height Adapters
To match height of the InRow RP to
various rack heights, height adapters
are available for NetShelter 42U VX
and 48U SX racks.
Flex Hose Piping Kits
For hard piping to the chilled water
InRow RP, stainless steel flex piping
kits are available. The kits ship with
two 0.914 m (3 ft) or 1.828 m (6 ft)
pipes, depending on selection.
Connections are 1.25 in NPT to 1.5 in
NPSM, OFS female.