InRow RP Technical Data Manual24
Glycol Correction Factors
Altitude Correction Factors for InRow Products
Air-cooled Performance Specifications
Performance Criteria Glycol Solution Percent Weight of Solution ***
0 10% 20% 30% 40% 50%
Capacity* Ethylene 1.00 0.97 0.93 0.88 0.81 0.75
Propylene 1.00 0.96 0.90 0.82 0.77 0.74
Pressure Drop** Ethylene 1.00 1.04 1.13 1.21 1.31 1.41
Propylene 1.00 1.09 1.20 1.35 1.52 1.67
All correction factors are based on unit entering conditions of 29.4°C (85°F) DB, 18.1 °C (64.5°F) WB, 1368.6 L/S (6950 CFM), 1.72
L/S (27.3 GPM), and 7.2°C (45°F) EFT.
*Multiply capacity of device or system by factor above for % solution.
**Multiply pressure drop of system by factor above for % solution.
***Glycol concentrations over 50% are not recommended.
Room Condition: 72 DB/50% RH
Altitude - m (ft) 0 305
(1000)
610
(2000)
915
(3000)
1219
(4000)
1524
(5000)
1829
(6000)
2134
(7000)
2438
(8000)
2743
(9000)
3048
(10000)
Specific volume - cm
3
/g
(ft
3
/lb)
847.77
(13.58)
879.61
(14.09)
912.70
(14.62)
947.66
(15.18)
983.86
(15.76)
1021.32
(16.36)
1061.28
(17.00)
1103.10
(17.67)
1146.80
(18.37)
1193.00
(19.11)
1241.69
(19.89)
Density - g/m
3
(lb/ft
3
) 1185.37
(0.074)
1137.31
(0.071)
1089.26
(0.068)
1057.22
(0.066)
1009.16
(0.063)
977.13
(0.061)
945.10
(0.059)
913.05
(0.057)
865.00
(0.054)
832.97
(0.052)
800.92
(0.050)
Density Ratio 1.000 0.964 0.929 0.895 0.862 0.830 0.799 0.769 0.739 0.711 0.683
Capacity Correction 1.000 0.981 0.962 0.933 0.913 0.884 0.865 0.846 0.826 0.807 0.787
Density ratio is used for air flow correction factor.
Capacity correction is used for performance derate.
NET COOLING CAPACITY
Entering Air Temperature ACRP 100 Series
22.2°C DB, 15.5°C WB (72°F DB, 60°F WB)
Total - kW (BTU/hr) 22.8 (78,000)
Sensible - kW (BTU/hr) 19.0 (65,000)
23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB)
Total - kW (BTU/hr) 25.2 (86,000)
Sensible - kW (BTU/hr) 21.7 (74,000)
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
Total - kW (BTU/hr) 26.9 (92,000)
Sensible - kW (BTU/hr) 26.9 (92,000)
29.4°C DB, 18.1°C WB (85°F DB, 64.6°F WB)
Total - kW (BTU/hr) 29.0 (99,000)
Sensible - kW (BTU/hr) 29.0 (99,000)
32.2°C DB, 19.0°C WB (90°F DB, 66.2°F WB)
Total - kW (BTU/hr) 30.5 (104,000)
Sensible - kW (BTU/hr) 30.5 (104,000)
35.0°C DB, 19.9°C WB (95°F DB, 67.8°F WB)
Total - kW (BTU/hr) 33.7 (115,000)
Sensible - kW (BTU/hr) 33.7 (115,000)
37.8°C DB, 20.7°C WB (100°F DB, 69.3°F WB)
Total - kW (BTU/hr) 36.9 (126,000)
Sensible - kW (BTU/hr) 36.9 (126,000)
40.6°C DB, 21.6°C WB) (105°F DB, 70.8°F WB*
Total - kW (BTU/hr) 36.6 (125,000)
Sensible - kW (BTU/hr) 36.6 (125,000)
*Airflow reduced to 4000 SCFM at this condition to maintain adequate return gas temperature.
Note: Unit is not recommended for use with total loads of 10 kW or less.
Note: Shaded lines represent leaving air temperatures above ASHRAE specifications of 25°C (77º F) at maximum airflow.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).