APC ACRP101 Water Dispenser User Manual


 
21InRow RP Technical Data Manual
Chilled Water Performance Specifications 12.8°C (55°F) EWT
Temperature dry bulb
(DB), wet bulb (WB)
°C (°F)
CW Delta T
°C (°F)
Total Net
Capacity
kW (BTU/hr)
Sensible Net
Capacity
kW (BTU/hr)
Sensible Heat
Ratio
SHR
CW Flow Rate
l/s (GPM)
Total CW
Pressure
Drop
kPa (ft
H
2
O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5 (10) 24.7 (85,000) 24.7 (85,000) 1.00 1.2 (18.3) 33 (11.3)
6.6 (12) 22.3 (76,000) 22.3 (76,000) 1.00 0.9 (13.9) 20 (6.7)
7.7 (14) 20.0 (68,000) 20.0 (68,000) 1.00 0.7 (10.8) 12 (4.2)
8.8 (16) 17.8 (61,000) 17.8 (61,000) 1.00 0.5 (8.6) 8 (2.8)
10 (18) 15.8 (54,000) 15.8 (54,000) 1.00 0.4 (6.9) 5 (1.8)
11.1 (20) 13.9 (48,000) 13.9 (48,000) 1.00 0.4 (5.6) 4 (1.2)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
5.5 (10) 31.3 (107,000) 31.3 (107,000) 1.00 1.4 (22.6) 50 (16.9)
6.6 (12) 28.5 (97,000) 28.5 (97,000) 1.00 1.1 (17.3) 30 (10.2)
7.7 (14) 25.8 (88,000) 25.8 (88,000) 1.00 0.9 (13.6) 19 (6.5)
8.8 (16) 23.3 (80,000) 23.3 (80,000) 1.00 0.7 (10.8) 8 (4.2)
10 (18) 21.0 (72,000) 21.0 (72,000) 1.00 0.6 (8.8) 8 (2.8)
11.1 (20) 18.7 (64,000) 18.7 (64,000) 1.00 0.5 (7.2) 6 (1.8)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
5.5 (10) 39.1 (133,000) 39.1 (133,000) 1.00 1.7 (27.7) 75 (24.9)
6.6 (12) 35.9 (123,000) 35.9 (123,000) 1.00 1.3 (21.3) 45 (15.02)
7.7 (14) 32.8 (112,000) 32.8 (112,000) 1.00 1.1 (16.9) 29 (9.7)
8.8 (16) 30.0 (102,000) 30.0 (102,000) 1.00 0.9 (13.6) 19 (6.5)
10 (18) 27.2 (93,000) 27.2 (93,000) 1.00 0.7 (11.1) 13 (4.4)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
6.6 (12) 44.2 (151,000) 44.2 (151,000) 1.00 1.6 (25.9) 66 (21.9)
7.7 (14) 40.8 (139,000) 40.8 (139,000) 1.00 1.3 (20.6) 42 (14.1)
8.8 (16) 37.5 (128,000) 37.5 (128,000) 1.00 1.1 (16.7) 28 (9.5)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
7.7 (14) 49.8 (170,000) 49.8 (170,000) 1.00 1.6 (24.8) 60 (20.1)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
7.7 (14) 59.7 (204,000) 59.7 (204,000) 1.00 1.9 (29.5) 84 (28.2)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak
conditions.
* To convert feet of water to PSIG, use the following formula: ft H
2
O ÷ 2.307 = PSIG.