23InRow RP Technical Data Manual
Chilled Water Data - General
MODEL ACRP 500 Series
MODULATING VALVES
Size -3 Way Ball Valve - NPT mm (in) 25.4 (1)
AIR SYSTEM - FANS (Standard Filter Installed)
Air Volume - l/s (SCFM) 3162 (6700)
Fan Motor - W (HP) 1100 (1.5)
Number of Fans 3
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
(ft
2
)
0.74 (7.9)
Rows Deep 4
Fins per meter (Fins per inch) 468 (12)
HUMIDIFICATION - SOLID STATE ELECTRODE CANISTER
Flush Cycle Automatic
Capacity - kg/hr (lbs/hr) 3.0 (6.6)
kW 2.25
REHEAT
Electric - Equally Loaded Three Stage, Finned Tubular, Low-Watt Density
Capacity - kW (BTU/hr) 9.0 (30,700)
Stages 3
FILTERS - PLEATED (STANDARD)
Quantity 4
Size - mm (in) 418 x 470 (16.45 x 18.5)
Depth - mm (in) 96 (3.78)
Efficiency (%) 30
FILTERS - PLEATED (OPTIONAL)
Quantity 4
Size - mm (in) 418 x 470 (16.45 x 18.5)
Depth - mm (in) 96 (3.78)
Efficiency (%) 85
PHYSICAL DATA
Weight - kg (lbs) 352 (776)
Height - mm (in) 1991 (78.40)
Width - mm (in) 600 (23.62)
Depth - mm (in) 1070 (42.13)
CONNECTION SIZES
Chilled Water
Supply Line - mm (in) 35.0 (1 3/8)
Return Line - mm (in) 35.0 (1 3/8)
Humidifier
Supply Line - mm (in) 6.35 (1/4)
Condensate Drain
Drain Line - mm (in) 12.7 (1/2)
For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak
conditions.
Maximum working pressure for the unit is 300 psig (2068.4 kPa).
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).