Operator Interface Products
HMi Operator Interface
Software and Accessories
Table 12. HMIEC0806/HMIEC1612 Function Specifications
M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the
special auxiliary relays (special M).
Item Specifications Remark
Control Method Stored program, cyclic
scan system
I/O Processing Method Batch I/O (refresh) Immediate refresh command available only
with I/O of the MPU
Execution Speed Basic command (30 us) Application command (30 ~ hundreds us)
Program Language Commands + Ladder
Diagram + SFC
Step commands included
Program Capacity 999 Steps Built-in EEPROM
Commands Basic commands: 32
(including the STL
commands)
Application commands: 59
Step Relay
(Latched)
General Step
Point
128 Points S0 ~ S127
Auxiliary
Relay
General 1024 Points M0 ~ M511, M768 ~ M999, 744 points;
M1000 ~ M1279, 280 points
Latched 256 Points M512 ~ M767
Timer Digital 64 Points T0 ~ T63 (100 ms time base)
63 Points T64 ~ T126 (10 ms time base)
1 Points T127 (1 ms time base)
Counter General 112 Points C0 ~ C111
Latched 16 Points C112 ~ C127
32 bit 13 Points C235,C236,C237,C238,C241,C242,
C244,C246,C247,C249,C251,C252, C254
(all of them are latched type)
Data
Register
General 408 Points D0 ~ D407
Latched 192 Points D408 ~ D599
Pointer P 64 Points P0 ~ P63
Index
Register
E / F 2 E, F
Constant Decimal K 16 bit: -32768 ~ +32767 32 bit: -2147483648 ~ +2147483647
Hexadecimal H 16 bit: 0000 ~ FFFF 32 bit: 00000000 ~ FFFFFFFF
Self Diagnosis / Protection I/O check, system execution timeout check, invalid command check,
program check and password settings
Monitor / Debug Program execution time display, bit / word, device settings