Eaton Electrical CA04801001E Dishwasher User Manual


 
CA04801001E For more information visit: www.eaton.com
13
Operator Interface Products
March 2008
HMi Operator Interface
Software and Accessories
Table 13. HMIEC0806/HMIEC1612 Electrical Specifications
Product Selection
Table 14. Product Selection — Software and Accessories
Item / Model Name HMIEC0806 HMIEC1612
Power Supply Voltage 5V DC, 1A (supplied by HMi)
Power Consumption 0.25W 0.5W
Noise Immunity
RS
CS
ESD
EFT
Surge
Frequency: 80MHz ~ 1GHz, 1.4GHz ~ 2.0GHz, Test level 10V/m
Frequency: 0.15MHz ~ 80MHz, Test level 10V
(HMi power port & I/O line)
Air discharge ±8 kV
±1.5 kV (HMI power port), ± 1 kV (I/O line)
±2 kV (HMI power port)
Ambient
Temperature/Humidity
Operation: 0°C ~ 50°C (Temperature), 10 ~ 90% (Humidity),
Storage: -40°C ~ 85°C (Temperature), 10 ~ 90% (Humidity)
Vibration / Shock IEC 61131-2 Compliant
5 Hz f < 9 Hz = Continuous: 1.75mm / Occasional: 3.5mm
9 Hz f 150 Hz = Continuous: 0.5g / Occasional: 1.0g
X, Y, Z directions for 10 times
Weight Approx. 95.5g Approx. 116g
Input Point Electric Specifications
Input Type DC (SINK or SOURCE)
Input Voltage 24V DC (5mA)
Active Level Off On, above 16V DC
On Off, below 14.4V DC
Response Time Approx. 10 mS
Output Point Electric Specifications
Output Type Relay-R
Current Specifications 1.5A / 1 Point (5A/COM)
Voltage Specifications 250V AC, below 30V DC
Maximum Loading 75 VA (Inductive), 90W (Resistive)
Response Time Approx. 10 mS
Mechanical Life 2 – 107 times (without load)
Electrical Life 100,000 times (3A 250V AC/30V DC)
6,000 times (5A 250V AC/30V DC)
Description Catalog
Number
Price
U.S. $
Programming Software HMISOFT 205.
Ethernet Modbus TCP Expansion Module HMIECENT 350.
I/O Expansion Module, 8 In/6 Out HMIEC0806 145.
I/O Expansion Module, 16 In/12 Out HMIEC1216 205.
6" Adapter Plate for PM1000 APPM1HMI6 202.00
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . PM-1