Garland BH/IN 2500 Cooktop User Manual


 
Part # 4520898 (03/31/11) Page 13
Fresh Air Intake Installation
The built-in induction units require a cooling air intake to
operate eectively. The air intake housing is mounted to
the cabinet, and is tted with a removable stainless steel
grease lter that can be cleaned in a dishwasher. Install the
air intake housing and connect it to the induction unit with
the aluminum air duct. Maximum length of this air inlet is
to be 96” (8’). Make sure the cabinet is also equipped with
a louvered air exhaust having a size of no less than 30 sq
inches (50 sq inches for dual units) for the hot air to escape
(by installer). Failure to provide adequate ventilation for the
unit will result in the unit overheating, nuisance shut down
and potential failure of the unit. (See Figures # 1 & 2)
Figure #  - Air Intake Housing
9"
[288.6 mm]
8 3/16"
[208 mm]
11" [279.4mm]
10 3/16" [258.8mm]
5/32"
[4mm]
FRONT VIEW
TOP VIEW
4 Holes
See Cut out for air intake housing on next page
INSTALLATION continued
Cut Out Opening
Louvered
Air Exhaust
Opening
(By Installer)
Aluminum air duct
(Max 96" (8'))
mounted on collars
with hose clamps
Removable grease lter and air
intake housing mounted on
cabinet
Fresh Air Supply
Air Intake Housing
See Fig. # 2
Sleeve with hose clip:
mounted to cabinet
Sleeve with hose clip:
mounted on bottom of unit
Silicone
Figure # 