Hoshizaki KM-1301SRH/3 Ice Maker User Manual


 
5
3. Controls and Adjustments
CAUTION
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact
Hoshizaki Technical Support at 1-800-33-1940.
a) Default Dip Switch Settings
The dip switches are factory set to the following positions:
S4 Dip Switch
S4 Dip Switch No. 1 2 3 4 5 6 7 8 9 10
KM-1301SAH/3
OFF OFF ON ON ON ON ON OFF OFF OFF
KM-1301SWH/3
OFF OFF ON ON ON ON ON OFF OFF OFF
KM-1301SRH/3
OFF OFF ON ON ON ON ON OFF ON OFF
S5 Dip Switch (Do Not Adjust)
S5 Dip Switch No.
1 2 3 4 5
KM-1301SAH/3 OFF OFF OFF OFF OFF
KM-1301SWH/3 OFF OFF OFF OFF OFF
KM-1301SRH/3 OFF OFF OFF OFF OFF
Freeze Timer (9 & 10)
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
(Do not adjust to 3 off and 4 on)
Harvest Timer (1 & )
Harvest Pump Timer (7)
(Do not adjust)
Factory Use (8)
b) Harvest Timer (S4 dip switch 1 & 2)
The harvest timer starts when the thermistor reads 48°F (9°C) at the evaporator outlet
and the control board reads the thermistor's 3.9 KΩ signal. The harvest timer is factory
set, and generally no adjustment is required. However, a setting longer than the factory
setting may be advised in cases where the ush provided at harvest needs to be
prolonged for extra cleaning. Before changing this setting, contact Hoshizaki Technical
Support at 1-800-33-1940 for recommendations. Keep in mind that setting the harvest
timer to a longer setting decreases 4-hour production.
S4 Dip Switch Setting Time
(seconds)
No. 1 No. 2
OFF OFF 60
ON OFF 90
OFF ON 10
ON ON 180