Hoshizaki KM-1301SRH/3 Ice Maker User Manual


 
50
3) 1-Minute Fill Cycle – LED 4 is on. WV and X relay (auxiliary code T-0, U-0),
X11 relay (auxiliary code U-1 and later) energize and the 1-minute ll cycle begins.
After 1 minute, CB checks for a closed F/S. If F/S is closed, the harvest cycle begins. If
closed, continue to step 4. If open, WV remains energized through additional 1-minute
ll cycles until water lls the tank and closes F/S (low water safety). Diagnosis: If WV
does not open, check the supply voltage at WV terminals, check continuity on the
coil, conrm the screen or external lter isn't plugged (no water ow). If unit fails to
start harvest, check for open F/S or bad 1-minute timer in CB. See "IV.D. Float Switch
Check and Cleaning" and "IV.B. Control Board Check."
4) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X relay (auxiliary code
T-0, U-0), X11 relay (auxiliary code U-1 and later) remain energized, HGV, X1 relay
(auxiliary code T-0, U-0), X10 relay (auxiliary code U-1 and later), Comp, and FMR
energize. CB monitors the warming of the evaporator via the thermistor located on the
suction line. When the thermistor reaches 48°F (9°C), CB reads a 3.9 kΩ signal from
the thermistor and turns harvest termination over to the harvest timer (S4 dip switch
1 & ). The harvest timer has settings of 60, 90, 10, and 180 seconds. For details,
see "II.C.3.b) Harvest Timer (S4 dip switch 1 & )." When the harvest timer expires,
the harvest cycle is complete. CB checks the position of F/S and proceeds to the next
cycle if it is closed, or calls for a 1-minute ll cycle if it is open. The minimum total time
allowed by CB for a complete harvest cycle is  minutes.
WV is energized during harvest for a maximum of 6 minutes or the length of harvest
minus 0 or 50 seconds (harvest pump timer (S4 dip switch 7)), whichever is shorter.
LED 4 goes off when WV and X relay (auxiliary code T-0, U-0), X11 relay (auxiliary
code U-1 and later) de-energize. LED 3 comes on and PM energizes and runs for the
last 0 or 50 seconds of harvest depending on S4 dip switch 7 setting. CAUTION! Do
not adjust S4 dip switch 7 out of the factory default position on this model.
Adjustment outside of the factory default position may result in damage to the
icemaker. For details, see "II.C.3.e) Harvest Pump Timer (S4 dip switch 7)."
PM is energized through the #5 pin (DBu wire) on the CB K1 ten-pin connector and
the X1 relay (auxiliary code T-0, U-0), X10 relay (auxiliary code U-1 and later). When
the harvest timer expires, the harvest cycle is complete. CB checks the position of
F/S and proceeds to the next cycle if it is closed or calls for a 1-minute ll cycle if it is
open. The minimum total time allowed by CB for a complete harvest cycle is  minutes.
Diagnosis: Check if Comp is running, HGV and WV still energized. Average harvest
cycle at factory setting is  to 3 minutes. How long does initial harvest last? 1.5 minutes
after initial harvest begins, touch Comp discharge line. Is it hot? If not, check refrigerant
pressures and Comp operation. If it is hot, touch the inlet line to the evaporator. Is it
hot? If it is hot and the freeze cycle is not starting, check the harvest timer adjustment
(S4 dip switch 1 & ), the thermistor for open circuit, the discharge line temperature,
Comp efciency, and if HGV is fully open. For a thermistor check, see "IV.E. Thermistor
Check." Check that PM circulates water over evaporator for the last 50 seconds of
harvest. If not, check X1 relay (auxiliary code T-0, U-0), X10 relay (auxiliary code
U-1 and later) and S4 dip switch 3 & 4. If 1-minute ll cycle starts, see "IV.D. Float
Switch Check and Cleaning."