V. Removal and Replacement of Components
WARNING
. This unit should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
. Move the control switch to the "OFF" position and turn off the power supply
before servicing.
3. CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews
are securely in place after the unit is serviced. Make sure that none have
fallen into the storage bin.
4. Make sure all food zones in the icemaker and storage bin are clean after
the unit is serviced. For cleaning procedures, see "VI. Cleaning and
Maintenance."
A. Service for Refrigerant Lines
WARNING
. Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certied service personnel.
. Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
3. Use an electronic leak detector or soap bubbles to check for leaks. Add a
trace of refrigerant to the system (if using an electronic leak detector), and
then raise the pressure using nitrogen gas (40 PSIG). DO NOT use R-404A
as a mixture with pressurized air for leak testing.
CAUTION
. Do not leave the system open for longer than 5 minutes when replacing or
servicing parts. The Polyol Ester (POE) oils used in R-404A units can absorb
moisture quickly. Therefore it is important to prevent moisture from entering
the system when replacing or servicing parts.
. Always install a new drier every time the sealed refrigeration system is
opened.
3. Do not replace the drier until after all other repair or replacement has been
made. Install the new drier with the arrow on the drier in the direction of the
refrigerant ow.
4. When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 50°F (°C).
1. Refrigerant Recovery
The icemaker unit is provided with refrigerant access valves. Using proper refrigerant
practices, recover the refrigerant from the access valves and store it in an approved
container. Do not discharge the refrigerant into the atmosphere.