Cornelius MJ32-4 PC Beverage Dispenser User Manual


 
Troubleshooting Guide
16
Problem Probable Cause Remedy
COMPRESSOR RUNS BUT
NO COOLING. TRIPPING
OVERLOAD.
(Compressor shell is hot to
touch).
Condenser fan not running.
Inadequate air flow through
the dispenser.
Blocked condenser fins.
Ambient air over 100°F 38°C.
Defective overload.
Defective compressor.
Check that the condenser fan is
running. If the fan is binding or
turning slowly, an overload condition
will occur.
Air flow is top front in, exhaust out
the rear. NEVER PLACE
ANYTHING ON TOP OF THE
DISPENSER. This will block the
airflow over heating the compressor
and causing it to trip the overload.
Remove the rear bonnet and check
the condenser fins. If unit is run in a
dusty environment, condenser fins
can become clogged, stopping the air
flow.
Brush out and clean with vacuum.
If the dispenser is working in an
environment over 100° ambient or is
drawing in discharged air, during a
heavy period, the unit may trip the
overload.
Overload works on shell temperature
and amperage draw and can be
defective. Replace as needed.
Refrigeration technician will verify if
the compressor is defective and needs
to be replaced.
UNIT IS DISPENSING
CONCENTRATE ONLY
REFRIGERATION SYSTEM
HAS BEEN RUNNING FOR
EXTENDED PERIOD
WITHOUT SHUTTING OFF
FROZEN WATER COIL.
Insufficient water level in the
water bath.
Agitator motor not operating.
Improperly located ice bank
control sensor.
See the Start-up and Operation
Section of this manual. Be sure the
water bath is filled to fill line.
Check the agitator motor located on
the refrigeration deck. Be sure it is
plugged in and receiving power.
Check that the impeller is not
obstructed. Replace if needed.
Melt the ice bank and check the
location of the sensing bulb. Be sure
it is all the way down to the bottom
of the tube.