CODE REFERENCE
GAS CODE REFERENCE
Safe and satisfactory operation of this oven depends to a great extent upon its proper installation, and it should be
installed, as applicable in accordance with the National Fuel Gas Codes, ANSI Z223.1/NFPA 54, latest version,
Manufacturers’ installation Instructions and local municipal building codes.
1. The oven and its individual shut off valve must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of ½ psig (3.45kPa).
2. The oven must be isolated from the gas supply piping system by closing its individual manual shut off
valve during any pressure testing of the gas supply system at test pressures equal to or less than
½ psig (3.45kPa).
IN MASSACHUSETTS: The minimum length of a flexible gas supply hose is thirty-six (36”) inches.
IN CANADA: The installation of these appliances is to be in accordance with CSA B.149.1 latest version – Natural
Gas and Propane Installation Code – and/or local codes.
IN AUSTRALIA: To be installed in accordance with AS 5601-2004 and 4563-2004 Gas Installation Code.
ELECTRICAL CODE REFERENCE
When installed, this appliance must be electrically grounded and its installation must comply with the National
Electric Code, ANSI-NFPA 70, latest edition, the Manufacturers’ Installation Instructions, and applicable local
municipal building codes.
IN CANADA: All electrical connections are to be made in accordance with CSA C22.2 latest version – Canadian
Electrical Code and/or local codes.
ALL OTHER COUNTRIES: Local gas and/or electrical codes will prevail.
1. Strain Relief is provided with each oven. International Dealer/Distributors provide applicable power
cord/plug for each customer.
2. All pole disconnection switch 3mm open contact distance.
3. To prevent electrical shock, an equal potential bonding ground lug is provided in the back. This allows
the oven to be connected to an external bonding system.
4. If used as double or triple stack and each oven has its own disconnection switch, all switches should be
close together.
RESTRAINT REQUIREMENT – GAS OVEN(S) ON CASTERS, U.S. AND AUSTRALIA
1. The installation shall be made with a gas connector that complies with the Standard for Connectors for Movable
Gas Appliances, ANSI Z21.69 latest version, and a quick disconnect device that complies with the Standard for
Quick Disconnect Devices for Use With Gas Fuel, ANSI Z21.41 latest version.
IN CANADA: The installation shall be made with gas connectors that comply with Canadian Code CSA 6.16
latest version and quick disconnects complying to Canadian Code CSA 6.9 latest version.
IN AUSTRALIA: To be installed in accordance with AS 5601-2004 and 4563-2004 Gas Installation Code.
2. The installation of the restraint must limit the movement of the oven(s) without depending on the connector, the
quick disconnect device or its associated piping to limit the oven movement.
3. If the restraint must be disconnected
during maintenance or cleaning, it
must be reconnected after the oven
has been returned to its originally
installed position.
OPERATIONS
1. Screw lifting eye “B” of cable assembly
to hole “A”.
2. Screw eye bolt “C” of cable assembly
to stud in wall “D” or floor anchor “E”.
NOTE: Installation point is the same for
single and double stack oven(s).
WARNING
INT’L (CE):
!
This appliance must be properly grounded at time of installation. Failure to ensure
that this equipment is properly grounded can result in electrocution, dismemberment
or fatal injury.