Manitowoc Ice Q 1800 Ice Maker User Manual


 
35
Refrigeration System
Safety Limit #1
Freeze time exceeds 60 minutes for 3 consecutive freeze cycles.
Possible Cause Check/Correct
Improper installation See “Installation/Visual Inspection Checklist” on page 7-10
Water system Low water pressure (20 psi min.)
High water pressure (80 psi max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective water fill valve
Dirty/defective water dump valve
Defective water pump
Electrical system Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Contactor not energizing
Compressor electrically non-operational
Restricted condenser water
flow (water-cooled models)
Low water pressure (20 psi min.)
High water temperature (90°F/32.2°C max.)
Dirty condenser
Dirty/defective water regulating valve
Water regulating valve out of adjustment
Refrigeration system Non-Manitowoc components
Improper refrigerant charge
Defective hot gas valve
Defective compressor
TXV starving or flooding (check bulb mounting)
Non-condensables in refrigeration system
Plugged or restricted high side refrigerant lines or component
SAFETY LIMIT NOTES
Because there are many possible external problems, do not limit your diagnosis to only the items listed in
this chart.
A continuous run of 100 harvests automatically erases the safety limit code.
The control board will store and indicate only one safety limit – the last one exceeded.
If the toggle switch is moved to the OFF position and then back to the ICE position prior to reaching the
100-harvest point, the last safety limit exceeded will be indicated.
If the harvest light did not flash prior to the ice machine restarting, then the ice machine did not stop
because it exceeded a safety limit.