Water connection
This machine must be connected to
the water supply in accordance with
all national and local plumbing
codes.
Faucets and drain connections should
be situated as close to the machine as
possible, and be easily accessible.
All water supply pressures should be
between 30 and 145 psi. The machine
is supplied with 3 connection hoses
11.5 ft. (3.5 m) long with
3
/
4
" (19 mm)
female hose thread ends.
If shorter hoses are needed 5 ft. (1.5 m)
hoses are supplied with the machine.
Do not shorten hoses!
The machine cannot be operated with
an inflow pressure of less than 10 psi
flow pressure.
Requirements (refer to the
Installation Diagram for more
information)
1. Cold water connection:
One
1
/
2
" (13 mm) cold water supply line
with a standard
3
/
4
" (19 mm) male hose
thread faucet is needed. The cold water
supply hose is marked with blue tape.
2. Hot water connection:
One
1
/
2
" (19 mm) hot water supply line
with a standard
3
/
4
" male hose thread
faucet is needed. The water
temperature must not exceed 150 °F /
65 °C (recommended: 140 °F / 60 °C).
The hot water supply hose is marked
with red tape.
3. DI water connection
One
1
/
2
" (13 mm) deionized water
supply line with a standard
3
/
4
" (19 mm)
male hose thread faucet is needed. The
machine cannot be operated
conventionally with a pressure of less
than 10 psi flow pressure. In this case
the installation of an optional DI pump
is required. The DI water supply hose
is marked with green tape.
Plumbing