46
Electrical Requirements
Installation of the Earth Leakage Circuit Breaker
■
This appliance must be supplied with the proper voltage and frequency, and
connected to an individual, properly earthed branch circuit, protected by a circuit
breaker or fuse. (The rating plate is on the bottom of the appliance.)
■ This appliance is not tted with other means for disconnection from the supply
mains having a contact separation in all poles that provide full disconnection
under overvoltage category III conditions. Means for disconnection must be
incorporated in the xed wiring in accordance with the wiring rules.
■ Two-wire, single-phase A.C. 220-240 V, 40 A, 50 Hz electrical system must
be used. (It is also possible to use a four-wire, three-phase.) If connecting to
aluminum wiring, use connectors approved for use with aluminum wiring.
■ Check with the local utilities for electrical codes applied in the area. Failure to
wire the appliance according to governing codes may result in a hazardous
condition.
■ After installation, show the customer where the breaker for the appliance is
located.
■ In accordance with the electrical wiring rules, incorporate the earth
leakage circuit breaker in the home electrical wire.
■ Follow the specication of the earth leakage circuit breaker as follows.
Rated current: 40 A, rated sensitivity current: 30 mA
Electrical Work
WARNING
Electrical work must be performed by a legally qualied electrician.