HRX-OM-J049-A
Chapter 3 Transport and Installation
3.2 Installation HRG010-W HRG015-W
1st edition : Aug. 2006
Rev. A: May. 2007
3-14
Recommended piping installation
Table 3-6 Recommended Piping Installation
Size
No. Name
HRG010-W HRG015-W
1 Valve Rc1/2 Rc3/4
2 Y-shaped strainer Rc1/2 Rc3/4
3 Pressure gauge 0 to 1.0 MPa
4 Valve Rc3/4
5 Relieving valve Rc3/4, set from 0 to 0.5 MPa
6 Y-shaped strainer Rc3/4
7 Flow meter Rc3/4, 0 to 100 L/min
[Tips]
Optional accessories listed below are available for the relieving valves shown
in Fig. 3-12 “Recommended Piping Installation”. Separate order for optional
accessories is to be placed upon designing the piping system if used for
piping installation.
Table 3-7 Allied Products
Part No. Name Qty. Note
HRG-BP010 Bypass (relieving valve) piping set 1 set HRG010 optional accessory
HRG-BP015 Bypass (relieving valve) piping set 1 set HRG015 optional accessory
Fig. 3-13 Recommended Piping Installation
Load device
To the drain port
Circulating fluid OUT
Circulating fluid RETURN
Tank drain port
Port for overflow
Facility water IN
Facility water OUT
Auto supply port Fluid supply
Facility water