2.2 Clearance above and around domestic appliances
Extract from AS5601
REQUIREMENTS
1 Overhead clearances – (Measurement A)
Range hoods and exhaust fans shall be installed in accordance with the
manufacturer’s instructions. However, in no case shall the clearance between the
highest part of the hob of the cooking appliance and a range hood be less than
600 mm or, for an overhead exhaust fan, 750 mm.
Any other downward facing combustible surface less than 600 mm above the
highest part of the hob shall be protected for the full width and depth of the
cooking surface area in accordance with Clause 5.12.1.2. However, in no case
shall this clearance to any surface be less than 450 mm.
2 Side clearances – (Measurements B & C)
Where B, measured from the periphery of the nearest burner to any vertical
combustible surface, is less than 200 mm, the surface shall be protected in
accordance with Clause 5.12.1.2 to a height C of not less than 150 mm above
the hob for the full dimension (width or depth) of the cooking surface area. Where
the cooking appliance is fitted with a ‘splashback’, protection of the rear wall is
not required.
3 Additional requirements for Freestanding and Elevated Cooking Appliaces –
(Measurements D & E)
Where D, the distance from the periphery of the nearest burner to a horizontal
combustible surface is less than 200 mm, then E shall be 10 mm or more, or the
horizontal surface shall be above the trivet.