Smeg PA106SX Cooktop User Manual


 
Instructions for the installer
10
3 GAS CONNECTION
This appliance is suitable for installation with Natural Gas or
ULPG (propane). Refer to page 12 for the relevant burner
pressure and appropriate injector sizes. When the appliance is
to be connected to Natural Gas then the pressure regulator
supplied must be fitted to the gas inlet. A test point (fo
r
checking the gas pressure) is supplied either with the regulator
or as a separate fitting in the case of ULPG (propane)
appliances.
Connection of the appliance to the gas supply must be in
accordance with the requirements of AS5601. A ½” BSP
connector at the inlet is recommended and the gas supply line
to the appliance must be of adequate length to allow sufficient
withdrawal of appliance for service or disconnection and be:
1. annealed copper pipe or;
2. flexible hose according to AS/NZ1869 & be at least
Class “B”, 10 mm diameter.
The appliance must be installed with provision to allow the gas to be turned off and
disconnected for servicing and removal of the appliance as required from the gas
supply.
Before the appliance is operated make certain all relevant parts are placed in the
correct position.
When the installation is completed the installation connections of appliance will require
to be leak tested, the burner operating pressure and flame checked and adjusted.
Warranty service calls do not cover these adjustments!
To check the operating pressure of the appliance it is recommended at least 2 large
size burners are used. Ensure appliance is secured to wall when installation is
completed.
N.G. The regulator supplied must be fitted to the ½ BSP thread at the rear of the
appliance. An approved manual shut-off valve must be installed. The N.G. regulato
r
must be checked and adjusted to 1.0kPa after installation.
ULPG: Can be connected to the inlet fitting directly. The
pressure must be checked to ensure it is operating at
2.75kPa. A separate test point fitting must be installed
between the piping & the appliance for the pressure to be
checked to ensure it is operating at 2.75kPa.