3
Step 1: Ventilation Requirements
It is strongly recommended that a
suitable exhaust hood be installed
above the range. Downdraft
ventilation should not be used.
The table below indicates the
Thermador hoods, by model
number, that are recommended
for use with all ranges.
1. Select Hood and
Blower Models:
• For wall installations, the hood
width must, at a minimum,
equal the width of the range
cooking surface. Where space
permits, a hood larger in width
than the cooking surface may
be desirable for improved ven-
tilation performance.
• For island installations, the
hood width should, at a mini-
mum, overhang the range
cooking surface by 6" on each
side.
Notes: * For wall installations where adequate space is available, the installer or user may elect to
use a hood that is wider than the range cooking surface. This may be particularly beneficial
for those cases, such as a long duct run or heavy usage of the grill, in which improved
capturing of the cooking exhaust is desired.
** Thermador offers a choice of remote (VTR1000Q or VTR1400Q) or in-hood (VTN1000Q)
blowers for use in wall installations.
VTR1000Q, VTR1400Q
or VTN 1000Q
VTR1000Q, VTR1400Q
VTR1000Q, VTR1400Q
36" RANGE
HTNI42YS
HNI42YS
PHI48ZS
VTR1000Q
VTR1400Q
PH36ZS, 42ZS
PHE36,42
HNW36YS
HNW42 YS
WALL INSTALLATION ISLAND INSTALLATION
RANGE WIDTH
HOOD* BLOWER** HOOD BLOWER
30" RANGE PH30ZS
PH30HQS
PHE30,36
VTR1000Q,
VTR1400Q
OR VTN 1000Q
HTNI42YS
HNI42YS
PHI48ZS
VTR1000Q,
VTR1400Q
48" RANGE
PH48ZS
PH48HQS
PHE48,60
VTR1000Q
VTR1400Q
or VTN 1000Q
HTNI48YS
HNI48YS
HTNI54YS
HNI54YS
PHI60ZS
VTR1400Q
2. Hood Placement:
• For best smoke elimination,
the lower edge of the hood
should be installed a minimum
of 30" to a maximum of 36"
above the range cooking sur-
face. (See Fig. 1).
• If the hood contains any com-
bustible materials (i.e. a wood
covering), it must be a mini-
mum of 36" above the cooking
surface.
3. Consider Make-Up Air:
• Due to the high volume of ven-
tilation air, a source of outside
replacement air is recom-
mended. This is particularly
important for tightly sealed and
insulated homes.
• A qualified heating and venti-
lating contractor should be
consulted.
IMPORTANT:
Ventilation hoods and blowers are
designed for use with single wall
ducting. However, some local
building codes or inspectors may
require double wall ducting. Con-
sult local building codes and/or
local agencies, before starting, to
assure that hood and duct instal-
lation will meet local requirements.
• Hood blower speeds should
be variable to reduce noise
and loss of heated or air con-
ditioned household air when
maximum ventilation is not
required. Normally, the maxi-
mum blower speed is only re-
quired when using the grill.