Trane fin prc003en Oven User Manual


 
FIN-PRC003-EN10
Controls
Description Single Pole
Catalog Number CB-ITS
Rated 25 amps at 120-277 VAC. 50-110°F
temperature range. Tamperproof and
adjustable through discharge louver.
Description Double Pole Thermostat
Catalog Number CB-ITD
Rated 25 amps at 120-277 VAC. 50-110°F
temperature range. Tamperproof and
adjustable through discharge louver.
Description Disconnect Switch
Catalog Number CB-IDS
Double pole rated 20 amps at 120-277
VAC.
Wiring
Diagrams
Model EWFB
Wiring Diagrams
Wiring Diagrams Control Section
Field Wiring With Integral Controls
Integral thermostats: wire entry from
either end.
Disconnect switch: mount either end.
Thermostat and disconnect: mount
either end.
Relays: control section.
Thermostat – disconnect and relay:
control section
Note: Control section is attached on
either side.
When heaters are furnished with
controls, make certain that the heater or
heaters do not exceed the lowest
amperage rating of the controls
furnished. For example, if a thermostat
and disconnect are furnished, the
thermostat is rated at 25 amps 240 and
277, the disconnect is rated 20 amps 240
and 277 VAC. Therefore, the combination
of heaters should not exceed 20 amps at
277 or 240 VAC.