Trane ZN.520 Ventilation Hood User Manual


 
62 UV-SVP01A-EN
Appendix—Unit Operation
Unit Operation Based On The Effective HEAT/COOL Output
Table 39: Unit operation based on the effective heat/cool output
Application mode input
(nviApplicMode)
Heat/cool mode input
(nviHeatCool)
Effective heat/ cool
mode output
(nvoHeatCool)
Unit Operation
Auto
Auto Determined by controller
Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Heat Heating
Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Enabled
Morning warm up Morning warm up
Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Disabled
Cooling Cooling
Fan—Enabled
Heating—Disabled
1
Cooling—Enabled
Damper—Enabled
Pre-cool Pre-cool
Fan—Enabled
Heating—Disabled
1
Cooling—Enabled
Damper—Disabled
Off Off
Fan—Disabled
Heating—Disabled
Cooling—Disabled
Damper—Disabled
Test Test
Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Fan only Fan only
Fan—Enabled
Heating—Disabled
Cooling—Disabled
Damper—Enabled
Not present Determined by controller Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Heat Any state Heating Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Enabled
Morning warm up Any state Morning warm up Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Disabled