Vulcan-Hart ML-136022 Electric Steamer User Manual


 
— 10 —
C24GA SERIES GAS CONVECTION STEAMERS
FLUE GAS EXHAUST
DO NOT obstruct the flow of flue gases from
the flue located on the rear of the steamer.
It is recommended that the flue gases be
vented to the outside of the building through
a ventilation system installed by qualified
personnel.
Information on the construction and installation
of ventilating hoods may be obtained from
Vapor Removal from Cooking Equipment,
NFPA-96 (latest edition) available from the
National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269.
The generator is equipped with a factory-
preset pressure regulator. Natural gas
pressure regulators are preset for 2.5" W.C.
(0.62 kPa). Propane gas pressure regulators
are preset for 10" W.C. (2.46 kPa). No further
adjustment should be required. Check gas
pressures with a manometer at time of
installation to verify that they agree with the
pressures specified.
WARNING: PRIOR TO LIGHTING, CHECK
ALL JOINTS IN THE GAS
SUPPLY LINE FOR LEAKS.
USE SOAP AND WATER
SOLUTION. DO NOT USE AN
OPEN FLAME.
After piping has been checked for leaks, all
piping receiving gas should be fully purged to
remove air.
Testing the Gas Supply System
When the gas supply pressure exceeds
1
/2 psig (3.45 kPa), the steamer and its
individual manual gas shutoff valve must be
disconnected from the gas supply piping
system.
When the gas supply pressure is
1
/2 psig (3.45
kPa) or less, the steamer should be isolated
from the gas supply system by closing its
individual manual gas shutoff valve.