Zephyr CTP-E 60SX Ventilation Hood User Manual


 
5
Installation - M ounting Height & Clearance
DUC T I NG
9"
36"
Min 98"-Max 124”
Min 28"-Max 36"
Min 34"-Max 52"
Minimummountheightbetween range top to hood bot-
tomshould be no less than 28".
Maximummountheight shouldbe no higher than 36".
It is importantto install the hoodat the propermounting
height.Hoods mountedtoo low could result in heat
damage and re hazard; while hoods mountedtoo high
willbe hard to reach and will loose its performance and
eciency.
If available,also refer to range manufacturer's height
clearance requirementsand recommendedhood
mountingheightabove range. Always check yourlocal
codes for any differences.
A minimumof 6” roundor 3-1 /4 x 10"
rectangular duct work must be used to maintain
maximumair ow eciency withthe 600 cfm
internalblower. A minimumof 10” to 8” roundmust
be used withthe 1000 cfm external blower.
Always use rigid type metalduct work only.
Flexible ducts couldrestrict air ow by up
to 50%.
Use calculation worksheet to computetotal
duct work.
ALWAYS, when possible, reduce the number
or transitions and turns. If a reducer is used,
install a long reducer instead of a pancake
reducer. Reduce duct size as far away from
openingas possible.
If turns or transitionsare required:
Install as far away from openingand as far
apart, between 2, as possible.
MinimumDuct Size:
Round - 6” minimumat 600 cfm
Round - 10” to 8” minimum
at
1000 cfm
Rect angular - 3 1/4” x 10” minimum only if
using internalblower at 600 cfm. Using
rectangular ductwork willrequire a transition
adapter (not provided, but readily available at
most hardware stores).
DAMAGE-SHIPME
NT/ IN
S
TAL
L
AT I ON:
Please fullyinspect unitfor damage
before installation.
If the unit is damaged in shipment , return
the unit to the store in which it was bought
for repair or replacement.
If the unit is damaged by the customer
,
repair or replacement is the responsibility
of the customer.
If the unit is damaged by the installer (if
other than the customer), repair of replace
ment must be made by arrangement
between customer and installer.
*Minimum ceiling height of 98”. Hood
mounted at 28” above cooking surface.
**Maximum ceiling height of 124". Hood
mounted at 36" above cooking surface.