Chapter 4 Parameters|
4-14 Revision July 2008, EG03, SW V1.06
Parameter Functions Settings
Factory
Setting
Customer
07-08 Calculate Total
Running Time of the
Motor (Min)
00 to 1439 Min 00
07-09 Calculate Total
Running Time of the
Motor (Day)
00 to 65535 Day 00
07-10 Electric Bill for One
Time
Read Only
Read
07-11 Accumulated Electric
Bill (per currency unit)
Read Only
Read
07-12 Accumulated Electric
Bill (per 10
4
currency
unit)
Read Only
Read
07-13 Electric Rate (per
currency unit)
0.01 to 655.35 0.6
Group 8 Special Parameters
Parameter Functions Settings
Factory
Setting
Customer
08-00 DC Braking Current
Level
00~100% 00
08-01 DC Braking Time
during Start-up
0.0~60.0 Sec 0.0
08-02 DC Braking Time
during Stopping
0.00~60.00 Hz 0.0
08-03 Start-point for DC
Braking
0.00~160.00 Hz 0.00
08-04 Momentary Power
Loss Operation
Selection
00: Disable
01: Trace from top downward
02: Trace from bottom upward
00
08-05 Maximum Allowable
Power Loss Time
0.1~5.0 Sec 2.0
08-06 Speed Search Time 0.1~5.0 Sec 0.5
08-07 Maximum Speed
Search Current
30~150% 110
08-08 BB speed search
method
00: Trace from top downward
01: Trace from bottom upward
00
08-09 Auto Restart Times
after Fault
00~10 00
08-10 Auto Restart Time after
Fault
00 to 60000 sec 600