ELECTRICAL
INSTALLATION
This appliance must be branch circuit protected
with proper ampacities, in accordance with the
wiring diagram. The Quickchiller must be properly
grounded in accordance with the National Electrical
Code and applicable local codes. Wire size for the
main incoming power to the unit must match the
minimum size listed in the specifications applicable
to the specific Quickchiller model. For supply
connections, locate the wire size listed in this manual.
Before operating the chiller, check all cable connections
in the electrical connection area for tightness since
connections can loosen during transport.
NOTE: After electrical connections have been
completed, operate the appliance in any
chilling mode for a period of 15 minutes
and recheck the main power connections
at the terminal block to make certain they
remain tight.
DANGER
To avoid electrical shock, this
appliance MUST be adequately
grounded in accordance with local
electrical codes or, in the absence of
local codes, with the current edition
of the National Electrical Code ANSI/
NFPA No. 70. In Canada, all electrical
connections are to be made in
accordance with CSA C22.1, Canadian
Electrical Code Part 1 or local codes.
DANGER
ELECTRICAL CONNECTIONS MUST
BE MADE BY A QUALIFIED SERVICE
TECHNICIAN IN ACCORDANCE WITH
APPLICABLE ELECTRICAL CODES.
voltage phase cycle/hz
QC-3 QC-20 QC-40 QC-50 QC-100
SELF-CONTAINED
208-240VAC 1 ph 50/60 Hz
recoMMeNded circuit aMperage:
recoMMeNded wire size:
20 amps
12/2 w.g.
20 amps
12/2 w.g.
30 amps
10/2 w.g.
40 amps
8/2 w.g.
60 amps
6/2 w.g.
no cord and plug
voltage phase cycle/hz
QC-3 QC-20 QC-40 QC-50 QC-100
SELF-CONTAINED
208-240VAC 3 ph 50/60 Hz
recoMMeNded circuit aMperage:
recoMMeNded wire size:
Not available Not available Not available
20 amps
12/3 w.g.
40 amps
8/3 w.g.
380-415VAC 3 ph 50/60 Hz
recoMMeNded circuit aMperage:
recoMMeNded wire size:
Not available Not available
30 amps
10/2 w.g.
Not available
30 amps
10/2 w.g.
no cord and plug
voltage phase cycle/hz
QC-3 QC-20 QC-40 QC-50 QC-100
REMOTE COMPRESSOR
(Cabinet Only)
208-240VAC 1 ph 50/60 Hz
recoMMeNded circuit aMperage:
recoMMeNded wire size:
Not available Not available Not available
20 amps
12/2 w.g.
30 amps
10/2 w.g.
no cord and plug
ELECTRICAL SPECIFICATIONS
Wire diagrams are located near the top of the unit, close to the compressor or control panel.