Honeywell PW-6000 Oven User Manual


 
PW-6000 Installation
Setting Up the PW-6000 Hardware
PW-6000 Installation Guide, Document 800-00005, Revision A 9
3.2 Setting the DIP Switches
Dual In-line Package (DIP) switches are read when the system powers up, except
where noted otherwise. The following table shows the setting options.
Table 2 PW-6000 DIP Switch Settings
S1
S2 S3 S4 Selection
OFF OFF OFF OFF Normal Operating Mode.
ON OFF OFF OFF When DIP switch 1 is ON, Port 0
communicates with the web browser.
Port 1 is used for RS-232/485
communications. After the panel
initialization, enable the default user
name (admin) and password (password).
The user name and password are read
dynamically; you do not need to reboot
the panel.
OFF ON OFF OFF Use the factory default communication
parameters.
ON ON OFF OFF Unless the network administrator
reserves an IP address for the panel
(based on the controller board’s Media
Access Control (MAC) address), the
PW-6000 uses Dynamic Host
Configuration Protocol (DHCP) to
obtain an IP address from the network
DHCP server.
When power is applied with the
switches in this position, there is a ten
second window (when LEDs 1and 2
flash alternately with LEDs 3 and 4),
during which memory is cleared if
switch 1 or switch 2 is changed to OFF.
When switch 1 or 2 is changed to OFF,
only LED 2 flashes and memory begins
to be cleared. This period of clearing
lasts several minutes. When the memory
has been cleared, the LED pattern
changes to the flashing of LEDs 1 and 4.
The panel then reboots by itself. All data
in memory is erased except the serial
number, MAC address, hardware
revision, and OEM code.