J. T. Eaton LCX9000 Beverage Dispenser User Manual


 
LCX9000 Liquid-Cooled Drives User Manual
3-2 For more information visit: www.EatonElectrical.com
MN04005001E
January 2007
Table 3-1: Cable Types Required to Meet Standards
Cable Data
Table 3-2: Cable Sizes 400 – 500V
Number of bolt connections = 2.
Number of bolt connections = 4.
See Main Terminal Cable Size.
Cable Type Level N/T
Mains Cable Power cable intended for fixed installation and the specific mains voltage.
Shielded cable not required.
Motor Cable Power cable intended for fixed installation and the specific mains voltage.
Shielded cable not required.
Control Cable Screened cable equipped with compact low-impedance shield.
Chassis
Catalog
Number I
th
Mains and
Motor Cable
Cu (mm
2
)
Terminal Cable Size
Max. Number of
Cables/Bolt Size
Main Terminal
(mm
2
), Max.
Ground Terminal
(mm
2
)
CH3 LCX016A0-4 16 3x2.5+2.5 50 1 – 10
LCX022A0-4 22 3x4+4 50 1 – 10
LCX031A0-4 31 3x6+6 50 1 – 10
LCX038A0-4
LCX045A0-4
38 – 45 3x10+10 50 Cu
50 Al
6 – 35
LCX061A0-4 61 3x16+16 50 Cu
50 Al
6 – 35
CH4 LCX072A0-4 72 3x25+16 50 Cu
50 Al
6 – 70 1/M8
LCX087A0-4 87 3x35+16 50 Cu
50 Al
6 – 70 1/M8
LCX105A0-4 105 3x50+25 50 Cu
50 Al
6 – 70 1/M8
LCX140A0-4 140 3x70+35 95 Cu/Al 25 – 95 1/M8
CH5 LCX168A0-4 168 3x95+50 185 Cu/Al 25 – 95 2/M10
LCX205A0-4 205 3x150+70 185 Cu/Al 25 – 95 2/M10
LCX261A0-4 261 3x185+95 or
2x(3x120+70)
185 Cu/Al 2 25 – 95 2/M10
CH61 LCX300A0-4 300 3x240+120
25 – 185 2/M12
LCX385A0-4 385 2x(3x120+70)
25 – 185 2/M12
CH62/72 LCX460A0-4 460 2x(3x150+70)
25 – 185 4/M12
LCX520A0-4 520 2x(3x185+95)
25 – 185 4/M12
LCX590A0-4
LCX650A0-4
590
650
3x(3x150+70)
25 – 185 4/M12
LCX730A0-4 730 3x(3x150+70)
25 – 185 4/M12