Liebert 3000 Refrigerator User Manual


 
Installation
8
Figure 5 Piping connections for split system fan coil units
SL-11900 PG 8
Piping outlet locations through the plenum are
the same as the unit. See below for
descriptions and connection sizes.
Humidifier Water Supply Line
1/4" OD CU
Suction Refrigerant Line
#11 Quick Connect on Models BU036E/BU035E
1 1/8" OD CU on Models BU060E/BU059E
Condensate Pump Line
1/2" OD CU
Used only if optional condensate
pump is ordered.
Hot Water Return
5/8" OD CU (optional)
Liquid Refrigerant Line
#6 Quick Connect on Models BU036E/BU035E
1/2" OD CU on Models BU060E/BU059E
Hot Water Supply
5/8" OD CU (optional)
Monitoring Panel
Condensate Drain
3/4" FPT
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without
a condensate pump have a factory-supplied trap in the unit, so a
field trap should not be added. Units with a condensate pump will
require a field-supplied trap downstream from the pump. The
drain line must comply with all applicable codes. (If condensate
pump is ordered piping is out top of unit).
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
UPFLOW (BU) MODELS