Split System Models
58
Figure 29 5 ton centrifugal air cooled condensing unit dimensional data (con't.)
DPN000226_Rev0
AIR COOLED
Heat rejection connection. Field-supplied
24V NEC Class 2 wiring. See Note 2. Wire
connections from evaporator module.
1. 24V GND
2. 24V supply
3. High pressure alarm (optional)
4. Hot gas bypass connection (only on
units with hot gas bypass)
NOTES:
1. Refer to specification sheet for full load amp and wire size amp ratings.
2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75’ (23m)
or not to exceed 1 volt drop in control line.
Field Supplied Unit Disconnect
Switch when Factory Unit
Disconnect Switch is not Supplied.
Connection terminal for field
supplied earth grounding wire
Removable Access Panels
Field Supplied 24V NEC Class 2 wiring
between condensing unit and fan/coil
unit
Low voltage electric power
supply conduit entrance
Electric service
not by Liebert
Optional Factory Installed
Disconnect Switch
Line Voltage Electric Power
Supply Conduit Voltage