Section 2 Installation Instructions
Part No. 80-1214-3 2-3
Location of Ice Machine
The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met,
select another location.
The location must be free of airborne and other
contaminants.
The air temperature must be at least 45°F (7°C), but
must not exceed 110°F (43.4°C).
The water temperature must be at least 45°F (7°C),
but must not exceed 90°F (32.2°C).
The location must not be near heat-generating
equipment or in direct sunlight.
The location must be capable of supporting the
weight of the ice machine and a full bin of ice.
The location must allow enough clearance for water,
drain and electrical connections in the rear of the ice
machine.
The location must not obstruct airflow through or
around the ice machine. QF400 airflow is in and out
of the front of the ice machine. Refer to below for
clearance requirements.
Ice Machine Head Section Clearance
Requirements
Ice Machine Heat of Rejection
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when sizing
the air conditioning equipment where self-contained air-
cooled ice machines are installed. QF2200/QF2300 ice
machines add an insignificant amount of load to a
conditioned space.
Location of Remote Condensing Unit
The location selected for the Remote Condensing Unit
must meet the following criteria. If any of these criteria
are not met, select another location.
The air temperature must be at least -20°F (-28.9°C)
but must not exceed 120°F (49°C).
The location must not allow exhaust fan heat and/or
grease to enter the condenser.
The location must not obstruct airflow through or
around the condensing unit. Refer to the chart below
for clearance requirements.
CONDENSING UNIT CLEARANCE REQUIREMENTS
QF400
Self-Contained
Air-Cooled
Self-Contained
Water-Cooled
Top/Sides 5” (12.7 mm) NA
Back 5” (12.7 mm) NA
QC700/QF800
Self-Contained
Air-Cooled
Self-Contained
Water-Cooled
Top/Sides 8” (20.3 mm) 5” (12.7 mm)
Back 5” (12.7 mm) 5” (12.7 mm)
QF2200/QF2300
Self-Contained
Air-Cooled
Remote
Air-Cooled
Top/Sides 8” (20.3 mm) 5” (12.7 mm)
Back 5” (12.7 mm) 5” (12.7 mm)
!
Caution
The ice machine head section must be protected if it
will be subjected to temperatures below 32°F (0°C).
Failure caused by exposure to freezing
temperatures is not covered by the warranty. See
“Removal from Service/Winterization”.
Series
Condensing Unit
Heat of Rejection*
QF400 4000
QF700 7800
QF800 7800
QF2200/RFC2085 21000
QF2300/RFC2385 21000
*B.T.U. / Hour
Ice Machine Condensing Unit
Top/Sides There is no minimum clearance required,
although 6” (12.7 cm) is recommended for
efficient operation and servicing only.
Front/Back 4’ (1.2)