Manitowoc Ice QF0400 Ice Maker User Manual


 
Section 6 Electrical System
Part No. 80-1214-3 6-13
Automatic Shut-Off
3A. ICE RUN OUT
Ice will build up in the bin until it
contacts the bin level probe. After ice
contacts the bin level probe for 30
continuous seconds the compressor
de-energizes. To allow excess ice to
run out, the gear motor and the water
float valve solenoid remain energized
for an additional 45 seconds, then
de-energize.
SV3126
RELAY
K1
GROUND
L1
L2 (N)
(21)
(65)
CONTACTOR
COIL
(90)
HIGH
PRESSURE
CUT-OUT
(95)
RELAY
K2
RELAY
K3
RELAY K4
(25)
10 AMP
FUSE
(46)
GEARMOTOR
(22)
(43)
(56)
WATER FLOAT
VALVE COIL
(52)
(22)
(55)
(51)
DUMP VALVE COIL
FAN MOTOR
(AIR-COOLED ONLY)
(41)
CONTACTOR
CONTACTS
L1 T1
C4
POTENTIA
L
RELAY
RUN
CAPACITO
R
C4
POTENTIAL
RELAY
CONTACTO
R
COIL
C4
POTENTIAL
RELAY
C4
POTENTIA
L
RELAY
(21)
RUN CAPACITOR
FAN CYCLE
CONTROL
OVERLOAD
COMPRESSOR
(49)
RUN
CAPACITOR
START
CAPACITOR
(31)
(62)
C5
C2
C1
C
R
S
(61)
(45)
3A. Ice Run Out (45 Seconds)
Toggle Switch ICE
Bin Level Probe Closed (Ice Contacting Probe)
Control Board Relays
#1 Contactor Coil Open / OFF
Compressor OFF
Condenser Fan Motor OFF
#2 Dump Valve OFF
#3 Gear Motor ON
#4 Water Float Valve Solenoid Coil ON
Revised 8/2003