4-3-6. Outdoor unit cycle defrost
Outdoor unit cycle defrost is performed in systems where 2 outdoor units are connected to the refrigerant system.
Description of outdoor unit cycle defrost
With this defrost method, when 1 outdoor unit operates in defrost mode (heat exchanger operating as a con-
denser), another outdoor unit operates as an evaporator in the same way as in ordinary heating mode.
In this way, the other outdoor unit is heating the unit where defrost is occurring. When 1 outdoor unit completes
defrost, the other outdoor unit performs defrost in the same way.
Because the amount of time that the unit operates as an evaporator is very short, there is little danger of frost
forming again quickly. Rather, because the heat source is very powerful, it is possible to shorten the defrost
operating time.
Defrost sequence
Outdoor unit cycle defrost is always completed in 2 defrost operations.
(A) When there are 2 outdoor units
Defrost
outdoor unit outdoor unit
Evaporator
outdoor unit outdoor unit
Defrost
First operation Second operation
Outdoor unit(s) where defrost occurs first
Outdoor compressor(s) where defrost occurs first
Outdoor unit(s) where defrost follows later
Outdoor compressor(s) where defrost follows later
Stopped indoor unit(s)
Indoor units where fan is operating
Heating mode indoor
units
Thermostat ON
Thermostat OFF
Time
Defrost
preparation
Defrost in
progress
Defrost in
progress
Defrost
preparation
E or S
OFF
OFF
S
Defrost
end
judgment
1 minMax. 6 minMax. 6 min
Defrost
end
judgment
OFF
1 min
E
E
OFF
S
C E or S
E C
E C
C E
1 min
1 - 12
4. Special Controls
W-2WAY ECO-i SYSTEM
Control Functions