Sanyo CHDX09663 Refrigerator User Manual


 
3
3 - 13
W-2WAY ECO-i SYSTEM
Outdoor Unit Maintenance Remote Controller
6. Mode Settings
N
Setting mode 2
<Operating procedure>
Press and hold the (CHECK) button, button, and button
simultaneously for 4 seconds or longer.
Press the temperature setting and buttons to change the item
code. The item codes and setting data are shown in the table below.
Press the timer time and buttons to change the setting data.
To confirm the changed setting data, press the
button.
(At this time, all displays stop blinking and remain lit.)
During this mode, “ ” is displayed, blinking. The display shows the set
outdoor unit address “System XX-YY” (System XX = System address, YY =
Address at outdoor unit sub-bus), item code number (DN value in the table
below), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The display changes between the first 4 digits (Fig.
A
) and the last 4
digits (Fig.
B
). When the first 4 digits are displayed, the top point of the colon is lit.)
To exit setting mode, press the (CHECK) button. Returns to the normal display mode.
A
B
1
5
3
2
List of Item Codes
DN Parameter Description
81 Outdoor unit capacity 0 = Disabled 224 = 72 Type 280 = 96 Type
1
2
5
3
Display of first 4 digits
<Refrigerant type>
A
and
B
are displayed alternately. (Example
shows 0000 0410 (R410A).)
Display of last 4 digits
Fig. 7