Specifications
Specification Value
Marley
/
Sigma Steel Cooling Tower
/
Specifications: Options
22
temperature and cold-fluid temperature
on two separate lines. The bypass shall
include a complete magnetic bypass
circuit and with capability to isolate the
VFDwheninthebypassmode.Transfer
to the bypass mode shall be manual in
theeventofVFDfailure.Oncethemotor
is transferred to the by-pass circuit the
fan motor will run at constant full speed.
The bypass circuit will not modulate ON
andOFFbasedonuidtemperature.The
application must be able to handle very
colduidtemperatureswhiletheVFD
is in a by-pass mode. Operator controls
shall be mounted on the front of the
enclosure and shall consist of start and
stopcontrol,bypass/VFDselection,Auto/
Manual selections, manual speed control.
To prevent heating problems in the fluid
cooloer fan motor and to assure proper
gearreducerlubricationtheVFDsystem
shall de energize the motor once 25%
motor speed is reached and cooling is no
longer required. The fluid cooler manu-
facturershallsupplyVFDstart-upassis-
tance. Tower vibration testing throughout
the speed range is required to identify
and lockout any natural frequency vibra-
tion levels which may exceed CTI guide-
lines.
Marley Premium VFD System
6.4 Add the following paragraph in the
Mechanical Equipment section when
VFD is used as a stand alone system:
A complete UL listed Variable Speed
Drive system in a NEMA 12 indoor
or NEMA 3R outdoor enclosure shall
beprovided.TheVFDshallusePWM
technology with IGBT switching and
integratedbypassdesign.VFDoutput
switching shall not cause mechanical
issues with gearbox teeth or drive shafts.
TheVFDshallcatchafanspinninginthe
reverse direction without tripping. The
panel shall include a main disconnect
with short circuit protection and external
operating handle, lockable in the off posi-
tion for safety. The system shall include
a solid state, PI temperature controller
to adjust frequency output of the drive
in response to the tower fluid tempera-
ture. The temperature of the fluid and
set point shall be displayed on the door
of the control panel. The bypass shall
include a complete magnetic bypass