SPX Cooling Technologies Marley Sigma Steel Ventilation Hood User Manual


 
Specifications
Specification Value
Marley
/
Sigma Steel Cooling Tower
/
Specifications: Options
26
Low Noise Tower:
1.1 Add the following at the end of this
paragraph: The cooling tower shall be
quiet operating, and shall produce an
overall level of sound no higher than ____
dBA at the critical location indicated on
the Plans.
Sound produced by a Sigma Steel tower operating in an unobstructed
environment will meet all but the most restrictive noise limitations –
and will react favorably to natural attenuation. Where the tower has
been sized to operate within an enclosure, the enclosure itself will have
a damping effect on sound. Sound also declines with distance – by
about 5 or 6 dBA each time the distance doubles. Where noise at a
critical point is likely to exceed an acceptable limit, you have several
options – listed below in ascending order of cost impact:
Where only a slight reduction in noise will satisfy — and the source
of concern is in a particular direction — merely turning the tower may
be the answer. Less sound emanates from the cased face of the tower
than does from the air intake face.
• In many cases, noise concerns are limited to nighttime, when ambi-
ent noise levels are lower and neighbors are trying to sleep. You can
usually resolve these situations by using two-speed motors in either
1800/900 or 1800/1200 RPM configuration; and operating the fans at
reduced speed without cycling “after hours”. (The natural nighttime
reduction in wet-bulb temperature makes this a very feasible solution
in most areas of the world, but the need to avoid cycling may cause
the cold water temperature to vary significantly.)
Variable speed drives automatically minimize the tower's noise level
during periods of reduced load and/or reduced ambient without sacri-
ficing the system's ability to maintain a constant cold water tempera-
ture. This is a relatively inexpensive solution, and can pay for itself
quickly in reduced energy costs.
Where noise is a concern at all times (for example, near a hospital),
the best solution is to oversize the tower so it can operate continu-
ously at reduced (1200 or 900 RPM) motor speed even at the highest
design wet-bulb temperature. Typical sound reductions are 7 dBA at
2/3 fan speed or 10 dBA at 1/2 fan speed, but larger reductions are
often possible.
• Extreme cases may require inlet and discharge sound attenuator
sections; however, the static pressure loss imposed by attenuators
may necessitate an increase in tower size. This is the least desirable
approach because of the significant cost impact – and because of the
obstruction to normal maintenance procedures.
Y
our Marley representative can help you meet your sound require-
ments.